Comparison list: 0 Article
Inquiry: 0 Article
(Illustration similar)
sl_sl00-3x3_on.jpg
sl_sl123_ip20_rueckseitig.tif

Type designation

SL00-3x3/185/KU00/2/IP20

Article number

L5066017

Size: NH00
Rated operating voltage Ue: 690 V
Rated operating current Ie: 160 A
Cable terminal: U box terminal KU00/2 2x10-50mm²
Busbar distance: 185 mm
Poles: 3
Switching mode: 3pole switchable
Quantity
Description
according to EN60947-3, size NH00 - 160A 3pole switchable for mounting on 3pole busbar system with 185mm centre-to-centre distance with steel frame clamp type KU00, max. clamping range: 10 - 95mm² for mounting on touch protected busbar systems
Quantity
Type:
SL00-3x3/185/KU00/2/IP20
Product Lifecycle:
Active product
Product standard:
IEC/DIN EN60947-3
Size:
NH00
Rated operating voltage Ue:
690 V
Rated operating current Ie:
160 A
Conv. free air thermal current with fuse-links Ith:
160 A
Conv. free air thermal current with solid links:
210 A
Rated frequency:
50 - 60 Hz
Rated isolation voltage Ui:
800 V
Total power loss at Ith (without fuse-link) Pv:
23 W
Power loss at 80% Ith (without fuse-link):
14.7 W
Utilization category 1:
690V - 160A - AC-22B
Utilization category 2:
500V - 160A - AC-23B
Utilization category 3:
400V - 160A - AC-23B
Rated impulse voltage Uimp:
8 kV
Rated conditional short-cirquit current Icc:
  • 100 (AC 690V)
  • 120 (AC 500V)
kA
Max. permissible power dissipation per fuse-link:
12 W
Ambient temperature:
-25 up to +70 (Attention derating of rated current required) °C
Type of Actuation:
Dependent manual operation
Altitude:
2000 m
Pollution degree:
3
Overvoltage category:
III
Mounting position:
user-defined
Electrical endurance (switching cycles):
200
Mechanical endurance (total switching cycles):
1,600
Degree of protection:
IP30
Direction of cable terminal:
bottom side
Applicable for fuse-links:
NH000, NH00
Cable terminal:
U box terminal KU00/2 2x10-50mm²
Busbar distance:
185 mm
Poles:
3
Special features:
For installation on busbar systems fitted with JEAN MÜLLER IP20-flat bar shroud systems;
(Installation in combination with IP20-shroud systems of other manufacturers on request)

Current measurement:
false
Hight:
662 mm
Width:
50 mm
Depth:
150 mm
Fuse monitoring:
None
ETIM - Code:
EC001040
Type:
SL00-3x3/185/KU00/2/IP20
Product Lifecycle:
Active product
Product standard:
IEC/DIN EN60947-3
Size:
NH00
Rated operating voltage Ue:
690 V
Rated operating current Ie:
160 A
Conv. free air thermal current with fuse-links Ith:
160 A
Conv. free air thermal current with solid links:
210 A
Rated frequency:
50 - 60 Hz
Rated isolation voltage Ui:
800 V
Total power loss at Ith (without fuse-link) Pv:
23 W
Power loss at 80% Ith (without fuse-link):
14.7 W
Utilization category 1:
690V - 160A - AC-22B
Utilization category 2:
500V - 160A - AC-23B
Utilization category 3:
400V - 160A - AC-23B
Rated impulse voltage Uimp:
8 kV
Rated conditional short-cirquit current Icc:
  • 100 (AC 690V)
  • 120 (AC 500V)
kA
Max. permissible power dissipation per fuse-link:
12 W
Ambient temperature:
-25 up to +70 (Attention derating of rated current required) °C
Type of Actuation:
Dependent manual operation
Altitude:
2000 m
Pollution degree:
3
Overvoltage category:
III
Mounting position:
user-defined
Electrical endurance (switching cycles):
200
Mechanical endurance (total switching cycles):
1,600
Degree of protection:
IP30
Direction of cable terminal:
bottom side
Applicable for fuse-links:
NH000, NH00
Cable terminal:
U box terminal KU00/2 2x10-50mm²
Busbar distance:
185 mm
Poles:
3
Special features:
For installation on busbar systems fitted with JEAN MÜLLER IP20-flat bar shroud systems;
(Installation in combination with IP20-shroud systems of other manufacturers on request)

Current measurement:
false
Hight:
662 mm
Width:
50 mm
Depth:
150 mm
Fuse monitoring:
None
ETIM - Code:
EC001040