Comparison list: 0 Article
Inquiry: 0 Article
(Illustration similar)

Type designation

DSL-60/183

Article number

G1741011

Type: DSL-60/183
Size: D02
Rated operating voltage Ue: 400 V
Rated operating current Ie: 63 A
Cable terminal: Elevator clamp F25 0,75-25mm²
busbar thickness: 5; 10 mm
Busbar width: 20; 30 mm
Poles: 3
Width: 36 mm
Quantity
Description
D-type switch-disconnector-fuses
Quantity
Type:
DSL-60/183
Product standard:
IEC/DIN EN60947-3
Size:
D02
Rated operating voltage Ue:
400 V
Rated operating current Ie:
63 A
Conv. free air thermal current with fuse-links Ith:
63 A
Rated frequency:
50 - 60 Hz
Rated isolation voltage Ui:
800 V
Total power loss at Ith (without fuse-link) Pv:
8 W
Utilization category:
AC-23B (63A/400V)
Rated impulse voltage Uimp:
8 kV
Rated conditional short-cirquit current Icc:
50 (AC 400V) kA
Max. permissible power dissipation per fuse-link:
5.5 W
Ambient temperature:
-25 up to +70 (Attention derating of rated current required) °C
Duty type:
Continuous duty
Altitude:
2000 m
Pollution degree:
3
Overvoltage category:
III
Mounting position:
vertical / horizontal
Electrical endurance (switching cycles):
300
Mechanical endurance (total switching cycles):
1,700
Degree of protection:
IP20
Applicable for fuse-links:
  • D01
  • D02
Thread:
E18
Cable terminal:
Elevator clamp F25 0,75-25mm²
Busbar distance:
60 mm
busbar thickness:
  • 5
  • 10
mm
Busbar width:
  • 20
  • 30
mm
Poles:
3
Width:
36 mm
Type:
DSL-60/183
Product standard:
IEC/DIN EN60947-3
Size:
D02
Rated operating voltage Ue:
400 V
Rated operating current Ie:
63 A
Conv. free air thermal current with fuse-links Ith:
63 A
Rated frequency:
50 - 60 Hz
Rated isolation voltage Ui:
800 V
Total power loss at Ith (without fuse-link) Pv:
8 W
Utilization category:
AC-23B (63A/400V)
Rated impulse voltage Uimp:
8 kV
Rated conditional short-cirquit current Icc:
50 (AC 400V) kA
Max. permissible power dissipation per fuse-link:
5.5 W
Ambient temperature:
-25 up to +70 (Attention derating of rated current required) °C
Duty type:
Continuous duty
Altitude:
2000 m
Pollution degree:
3
Overvoltage category:
III
Mounting position:
vertical / horizontal
Electrical endurance (switching cycles):
300
Mechanical endurance (total switching cycles):
1,700
Degree of protection:
IP20
Applicable for fuse-links:
  • D01
  • D02
Thread:
E18
Cable terminal:
Elevator clamp F25 0,75-25mm²
Busbar distance:
60 mm
busbar thickness:
  • 5
  • 10
mm
Busbar width:
  • 20
  • 30
mm
Poles:
3
Width:
36 mm